Condition assessment of power transformer insulation using short-duration time-domain dielectric spectroscopy measurement data

dc.campusKolkata
dc.contributor.authorMishra, Deepak
dc.contributor.authorBaral, Arijit
dc.contributor.authorHaque, Nasirul
dc.contributor.authorChakravorti
dc.date.accessioned2023-07-19T11:16:35Z
dc.date.accessioned2025-03-31T13:16:27Z
dc.date.available2023-07-19T11:16:35Z
dc.date.issued2019-10-14
dc.description.abstractUtilities prefer noninvasive methods for assessing the condition of power transformer insulation. Analysis of polarization-depolarization current (PDC) is one such popular method. One such analysis involves the estimation of trapped charge released from the interfacial region of oil-paper insulation. The literature shows that such charges can be reliably used for the diagnosis of transformer insulation. However, such analysis requires a complete profile of PDC. PDC measurement (an offline technique) takes a large amount of time (several hours) to complete. The magnitude of PDC data for a larger value of time is also sensitive to changes in environmental conditions and field noise as its magnitude is low. Hence, a reliable estimation of detrapped charge may require numerous PDC measurements. This situation is not convenient for utilities as it prolongs shut down time. In this article, a method has been proposed which is capable of estimating detrapping charge using PDC data measured for a short span of time. The proposed method is tested on data collected from several real-life in-service transformers.
dc.identifier.citationD. Mishra, A. Baral, N. Haque and S. Chakravorti, "Condition Assessment of Power Transformer Insulation Using Short-Duration Time-Domain Dielectric Spectroscopy Measurement Data," in IEEE Transactions on Instrumentation and Measurement, vol. 69, no. 7, pp. 4404-4411, July 2020, doi: 10.1109/TIM.2019.2947120.
dc.identifier.issn0018-9456
dc.identifier.issn1557-9662
dc.identifier.urihttps://ieeexplore.ieee.org/document/8867958
dc.identifier.urihttps://dspacenew8-imu.refread.com/handle/123456789/2294
dc.language.isoen_US
dc.publisherIEEE
dc.schoolSchool of Marine Engineering and Technology
dc.subjectCharge carriers
dc.subjectDielectric measurement
dc.subjectInsulation
dc.subjectPower transformers
dc.subjectTime-domain analysis
dc.titleCondition assessment of power transformer insulation using short-duration time-domain dielectric spectroscopy measurement data
dc.typeArticle