Estimation of de-trapped charge for diagnosis of transformer insulation using short-duration polarisation current employing detrended fluctuation analysis

dc.campusKolkata
dc.contributor.authorDutta, Saurabh
dc.contributor.authorMishra, Deepak
dc.contributor.authorBaral, Arijit
dc.contributor.authorChakravorti, Sivaji
dc.date.accessioned2023-07-20T05:14:09Z
dc.date.accessioned2025-03-31T10:51:20Z
dc.date.available2023-07-20T05:14:09Z
dc.date.issued2020-10-01
dc.description.abstractResearchers have shown that the value of charge carriers, de-trapped from the oil–paper interface of power transformer insulation, is useful in carrying out the diagnosis. However, the evaluation of the de-trapped charge requires the analysis of polarisation–depolarisation currents. Being an off-line time-consuming process, the measurement and analysis of polarisation and depolarisation current (PDC) data are not practically advantageous. The study presents a detrended fluctuation analysis-based technique to estimate the magnitude of normalised de-trapped charge using the polarisation current measured for a short duration. Using the proposed technique, the requirement of measuring the complete PDC data, for diagnosis purposes, can be eliminated. Further, the technique also eliminates the requirement of depolarisation current which in turn facilitates a reduction in equipment shutdown time. The applicability of the proposed technique is tested on the data obtained from several real-life power transformers.
dc.identifier.citationS. Dutta, D. Mishra, A.Baral, and S. Chakravorti, “Estimation of de-trapped charge for diagnosis of transformer insulation using short-duration polarisation current employing detrended fluctuation analysis”, IET High Voltage, Vol. 05, No. 5, pp.636-641, 2020. doi:https://doi.org/10.1049/hve.2019.0348
dc.identifier.issn2397-7264
dc.identifier.urihttps://dspacenew8-imu.refread.com/handle/123456789/2192
dc.language.isoen_US
dc.publisherThe Institution of Engineering and Technology
dc.schoolSchool of Marine Engineering and Technology
dc.subjectPower transformer insulation
dc.subjectTransformer oil
dc.subjectFluctuations
dc.subjectElectric current measurement
dc.titleEstimation of de-trapped charge for diagnosis of transformer insulation using short-duration polarisation current employing detrended fluctuation analysis
dc.typeArticle

Files

Original bundle

Now showing 1 - 1 of 1
No Thumbnail Available
Name:
High Voltage - 2020 - Dutta - Estimation of de‐trapped charge for diagnosis of transformer insulation using short‐duration.pdf
Size:
1.06 MB
Format:
Adobe Portable Document Format

License bundle

Now showing 1 - 1 of 1
No Thumbnail Available
Name:
license.txt
Size:
1.71 KB
Format:
Plain Text
Description:

Collections