Estimation of paper conductivity from short duration polarisation–depolarisation current for diagnosis of power transformer

dc.campusKolkata
dc.contributor.authorMishra, Deepak
dc.contributor.authorHaque, Nasirul
dc.contributor.authorBaral, Arijit
dc.contributor.authorChakravorti, Sivaji
dc.date.accessioned2023-07-20T04:24:23Z
dc.date.accessioned2025-03-31T16:57:57Z
dc.date.available2023-07-20T04:24:23Z
dc.date.issued2019-07-12
dc.description.abstractThe value of paper conductivity provides quantitative evaluation of transformer insulation health. However, proper identification of paper conductivity requires complete profile of polarisation–depolarisation current (PDC). PDC measurement being a time-consuming offline process generally takes several hours to complete. Furthermore, magnitude of PDC becomes very low at larger value of time, which makes it sensitive to changes in environmental conditions and field noise. Hence, accuracy of paper conductivity identification can be ensured by conducting multiple measurements. This in-turn prolongs shutdown time of equipment and become less advantageous to utilities. Here, a method is proposed which is capable of estimating paper conductivity using PDC data recorded for only 800 s. The proposed technique is tested on data collected from several real-life in-service transformers. In order to illustrate the accuracy of the proposed technique, paper conductivities (calculated from short duration PDC) were compared with those computed using PDC measured for 10,000 s.
dc.identifier.citationD. Mishra, N. Haque, A. Baral, and S. Chakravorti, “Estimation of Paper Conductivity from Short Duration Polarization Depolarization Current for Diagnosis of Power Transformer”, IET Science, Measurement and Technology, Vol.13, No. 8, pp.1178-1185, 2019. DOI: 10.1049/iet-smt.2019.0012
dc.identifier.issn1751-8822
dc.identifier.urihttps://dspacenew8-imu.refread.com/handle/123456789/2453
dc.language.isoen_US
dc.publisherThe Institution of Engineering and Technology
dc.schoolSchool of Marine Engineering and Technology
dc.subjectTransformers and reactors
dc.subjectOrganic insulation
dc.subjectCurrent measurement
dc.subjectImpedance and admittance measurement
dc.subjectElectrical instruments and techniques
dc.titleEstimation of paper conductivity from short duration polarisation–depolarisation current for diagnosis of power transformer
dc.typeArticle

Files

Original bundle

Now showing 1 - 1 of 1
No Thumbnail Available
Name:
IET Science Measure Tech - 2019 - Mishra - Estimation of paper conductivity from short duration polarisation.pdf
Size:
1.44 MB
Format:
Adobe Portable Document Format

License bundle

Now showing 1 - 1 of 1
No Thumbnail Available
Name:
license.txt
Size:
1.71 KB
Format:
Plain Text
Description:

Collections