Research Publications

Permanent URI for this communityhttps://dspacenew8-imu.refread.com/handle/123456789/127

Browse

Search Results

Now showing 1 - 10 of 14
  • Item
    A method to predict degree of polymerization value of oil-paper insulation using interfacial charge
    (IEEE, 2029-12-20) Singh, Vijeta; Mishra, Deepak; Baral, Arijit; Chakravorti, Sivaji
    Analysis based on Degree of Polymerization (DP) value is assumed to provide reliable regarding insulation condition. However, due to the invasive nature of testing, DP value based-analysis is not feasible in practical cases as it requires a paper sample from the in-service unit. Here, an attempt is made to develop a methodology to predict DP value based on non-invasive testing of oil-paper insulation. In this paper, it is found that DP value maintains a well-known relation with interfacial charge (estimated using Polarization Depolarization Current data) as both these parameters are related to the cellulosic condition. The proposed method successfully applied on various laboratory prepared samples containing different moisture content.
  • Item
    Estimation of performance parameters using charge freed from deep traps located at interfacial region of oil-paper insulation
    (IEEE, 2019-11-21) Mishra, Deepak; Verma, R.; Baral, Arijit; Haque, Nasirul; Chakravorti, Sivaji
    De-trapped charge dislodged from interfacial region of oil-paper insulation can be used as an effective insulation sensitive parameter. Over time, various physiochemical reactions takes place at interfacial region and consequently results in the formation of different trap sites (deep and shallow). Charges which resides at these traps sites are de- trapped after gaining sufficient energy. In present analysis, it is found that charge dislocated from deep traps maintains some specific type of relationship with different insulation sensitive parameters. Before using de-trapped (dislodge from deep traps) as an effective insulation sensitive parameter the effect of geometry must be reduced, as amount of de-trapped charge depends on the area of interfacial region which is not identical for all units. Result presented in this paper shows that use of geometric capacitance for normalization purposes significantly reduces the effects of insulation physical dimensions on de- trapped charge. The capability of deep charge (normalized using dc insulation resistance and geometrical capacitance) is also compared in the present work.
  • Item
    Effect of measurement temperature of insulation poles used for assessment of oil-paper insulation
    (IEEE, 2018-12-07) Verma, R.; Mishra, Deepak; Baral, Arijit; Chakravorti, Sivaji
    Analysis of Polarization-depolarization current (PDC) data is a popular technique used for assessing condition of oil-paper insulation. Oil-paper insulation deteriorates with aging during the operational life of the power equipment. In order to get information regarding the insulation condition; different performance parameters are used which can be estimated from PDC data. These parameters include paper moisture (%pm), Dissipation factor (%tanδ) and paper conductivity (σ paper ). In addition to these parameters, insulation poles can also be used for insulation diagnosis. Recently, it has gained popularity in field of insulation diagnosis as it does not depend on physical geometry of insulation. In this paper, the effect of measurement temperature on insulation poles has been analysed. Also, an attempt has been made to establish a relation between insulation poles and other insulation sensitive parameters such as %pm, σ paper and %tan δ.
  • Item
    Effect of measurement temperature on interfacial charge freed from deep traps located at the interface of oil-paper insulation
    (IEEE, 2018-12-07) Dey, Debangshu; Sarkar, A.; Pal, Sayantan; Kumar, A.; Mishra, Deepak; Baral, Arijit; Haque, Nasirul; Chakravorti, Sivaji
    Accumulation of interfacial charge creates local field distortion during insulation response measurement. Furthermore, such localized field enhancement affects the interaction between polar compounds present within oil-paper insulation and in turn affects its aging process. By getting sufficient trap energy (normally by thermal oscillation) these trapped charges dislocate from their locations and contribute in depolarization current. These interfacial charges include charges dislocated from shallow and deep sites at interfacial region. The charge residing at deep locations takes more time to dislodge themselves compared to charge residing at shallow sites. As dipole present in cellulose has large relaxation time, there might be some relation between deep charge and paper insulation sensitive parameters. In this work, effects of temperature on deep traps are analyzed. Results reported in this paper shows that magnitude of charge freed from deep locations maintains a correlation with measurement temperature and paper conductivity.
  • Item
    Feasibility of using normalized de-trapped charge for diagnosis of power transformer insulation
    (IEEE, 2018-10-07) Mishra, Deepak; Baral, Arijit; Haque, Nasirul; Chakravorti, Sivaji
    In order to use de-trapped interfacial charge as a performance parameter for diagnosis, it is necessary to reduce the influence of insulation geometry. Available literature shows that this can be done by considering dc insulation resistance R 0 as the normalization factor. Such normalization may not be always practically feasible as information regarding R 0 requires measurement of temperature sensitive low amplitude current. In this paper it is shown that geometric capacitance C 0 (instead of R 0 ) can be used as an effective normalization parameter to reduce effect of insulation geometry. Effect of normalizing freed interfacial charge using C 0 and R 0 and its subsequent effect on insulation diagnosis are presented in this paper.
  • Item
    Effect of interfacial charge on parameters considered for insulation diagnosis of power transformer
    (IEEE, 2017-12-02) Mishra, Deepak; Baral, Arijit; Pradhan, Arpan Kumar; Haque, Nasirul; Chakravorti, Sivaji
    Out of various analysis methods available Polarization Depolarization Current (PDC) measurement is extensively used for monitoring of oil-paper insulation health. In such case, Classical Debye Model (CDM) is used for analysis of recorded PDC data. CDM has limited capacity to simulate the effect of interfacial charge. Due to this interfacial charge, nonlinearity arises in the system which adversely affects the insulation. Conductivity difference between oil and paper is the main reason behind this interfacial charge which creates nonlinearity in system. In the present work, the effect of interfacial charge is analyzed on some of the performance parameters used for diagnosis of insulation like peak value of return voltage spectrum and paper conductivity.
  • Item
    Effect of charge accumulated at oil-paper interface on zero of transfer function formulated using classical debye model parameters
    (IEEE, 2017-11) Mishra, Deepak; Pradhan, Arpan Kumar; Baral, Arijit; Haque, Nasirul; Chakravorti, Sivaji
    PDC measurement and analysis is one of widely used tool for reliable diagnosis of power transformer insulation. In different reported methods of analysis it is considered that polarization current is composed of the current due to dipole movement and conduction current. Similarly the depolarization current is assumed to be composed of relaxation of dipoles. However when the dc conduction effect is removed from polarization current it is found the resulting current is not similar to the measured depolarization current. This deviation in both the currents show the presence of nonlinearity in the system. This nonlinearity arises due to migration of trapped charges that reside at the interfacial region of oil-paper insulation. The present paper shows the effect of such free charge on some important performance parameters like paper moisture and zero of Transfer Function of Classical Debye Model.
  • Item
    A novel method to predict severity of thermal aging and degree of polymerization for reliable diagnosis of dry-type insulation
    (IEEE, 2022-04) Mishra, Shalini; Baral, Arijit; Mishra, Deepak; Chakravorti, Sivaji
    The effect of thermal aging on Nomex-paper-based vacuum pressure impregnation (VPI) insulation is reported in this article. The frequency-dependent dielectric loss of Nomex-paper-based VPI dry insulation is affected after significant thermal aging. This variation in dielectric loss of the insulation maintains a good correlation with the duration of thermal aging. A new parameter sensitive to the severity of thermal aging is also introduced. To identify the parameter, the excitation voltage waveform and the corresponding insulation response at a given frequency are required. Determining the parameter does not require denoising of recorded waveforms, reducing the overall computational burden. Based on the newly introduced parameter, a cost-effective method is proposed to predict the dielectric loss and degree of polymerization (DP) in a thermally aged VPI-type dry insulation. The proposed method employs the intermediate frequency range and hence does not require time-consuming low-frequency measurements.
  • Item
    Prediction of insulation sensitive parameters of power transformer using detrended fluctuation analysis based method
    (IEEE, 2022-06) Dutta, Saurabh; Dey, Jagriti; Mishra, Deepak; Baral, Arijit; Chakravorti, Sivaji
    Utilities prefer to perform a condition-based assessment of power transformer insulation in the least possible shutdown time. It is essential to estimate the values of various insulation condition sensitive performance parameters with higher accuracy. In the present work, a technique for the estimation of performance parameters, moisture content of paper, dissipation factor of the entire oil-paper insulation, paper conductivity, and activation energy is proposed. The evaluation of these parameters using reported techniques requires complete measurement of polarization and depolarization current profile, which requires around 20000 s of measurement time. The present method uses a forecasted polarization current profile obtained from 600 s of measured polarization current data. Detrended Fluctuation Analysis is applied to the forecasted polarization current data obtained from various in-service power transformers to obtain a suitable parameter. It is shown that this parameter maintains well-defined relationships with parameters; moisture content of paper, dissipation factor of oil-paper insulation, paper conductivity, and activation energy. The proposed technique is beneficial for utilities as it eliminates the requirement of measuring depolarization current and return voltage measurement for estimating activation energy.
  • Item
    Assessment of interfacial charge accumulation in oil-paper interface in transformer insulation from polarization-depolarization current measurements
    (IEEE, 2017-06-03) Mishra, Deepak; Haque, Nasirul; Baral, Arijit; Chakravorti, Sivaji
    Accumulation of interfacial space charge in oil-paper interface is a critical issue in insulation diagnostics of transformers. This interfacial charge mainly accumulates due to the conductivity difference of oil and paper. Accumulation of interfacial charge leads to localized field enhancement, which further leads to partial discharges and acceleration in the aging of insulation. Therefore, from the point of view of transformer insulation diagnostics, assessment of interfacial charge is very important. However, it is not easy to estimate interfacial space charge behavior from the transformer diagnostics methods currently in use. In case of Polarization-Depolarization Current (PDC) measurement, a well known method for transformer condition monitoring, the effect of interfacial charge is reflected in the non-linearity of current response during polarization and de-polarization. During de-polarization process, a part of the interfacial charge accumulated during polarization period is absorbed by the electrodes producing a current, which is difficult to separate using conventional linear dielectric theory. In this paper, an attempt has been made to separate this current component from de-polarization current through considering charge de-trapping mechanism. Terming this current component as de-trapping current, its relationship with other parameters of transformer insulation is discussed. The developed methodology has been applied on several practical transformers. It was observed that the time constant of de-trapping current is related to the paper conductivity, oil conductivity, dissipation factor and age of the insulation.