Compensating the effect of residual dipole energy on dielectric response for effective diagnosis of power transformer insulation

dc.campusKolkata
dc.contributor.authorMishra, Deepak
dc.contributor.authorBaral, Arijit
dc.contributor.authorChakravorti, Sivaji
dc.date.accessioned2023-07-20T05:03:27Z
dc.date.accessioned2025-03-31T17:00:09Z
dc.date.available2023-07-20T05:03:27Z
dc.date.issued2017-11-28
dc.description.abstractAnalysis of relaxation current is a widely accepted method for diagnosis of power transformer insulation. The accuracy of such diagnostic tool is dependent on insulation model parameters which are formulated using relaxation current. This implies that the accuracy and hence the reliability of existing insulation diagnosis methods indirectly depends on the accuracy of the recorded polarisation depolarisation current. Sometimes during field measurement relaxation current measurement equipment fails to record proper current, even after application of dc charging voltage. As per utilities, this primarily happens due to improper/loose connections (this cannot be avoided entirely due to the involvement of human factors) and such situation is usually followed by checking and rectifying improper connection. The analysis presented in this study shows that the polarisation current recorded immediately after rectifying the correction is inaccurate and leads to the erroneous diagnosis. Furthermore, it is observed that in these cases, the measured and calculated (using insulation model) values of performance parameters like dissipation factor, polarisation index, and paper-moisture differ by a large extent. This work is aimed at removing the effect of this residual dipole energy introduced during the improper connection phase.
dc.identifier.citationD. Mishra, A. Baral, and S. Chakravorti, “Compensating the Effect of Residual Dipole Energy on Dielectric Response for Effective Diagnosis of Power Transformer Insulation”, IET Science, Measurement and Technology, Vol. 12, No. 3, pp.314 – 322, 2018. doi: 10.1049/iet-smt.2017.0216
dc.identifier.issn1751-8822
dc.identifier.urihttps://dspacenew8-imu.refread.com/handle/123456789/2506
dc.language.isoen_US
dc.publisherThe Institution of Engineering and Technology
dc.schoolSchool of Marine Engineering and Technology
dc.subjectTransformers and reactors
dc.subjectCurrent measurement
dc.subjectReliability
dc.subjectMeasurement of basic electric and magnetic variables
dc.subjectInsulation and insulating coatings
dc.titleCompensating the effect of residual dipole energy on dielectric response for effective diagnosis of power transformer insulation
dc.typeArticle

Files

Original bundle

Now showing 1 - 1 of 1
No Thumbnail Available
Name:
IET Science Measure Tech - 2018 - Mishra - Compensating the effect of residual dipole energy on dielectric response for.pdf
Size:
1.76 MB
Format:
Adobe Portable Document Format

License bundle

Now showing 1 - 1 of 1
No Thumbnail Available
Name:
license.txt
Size:
1.71 KB
Format:
Plain Text
Description:

Collections